ESM-9930
Descriptions | |
Approvals | UL Recognized Component (File No : E 254103), GOST-R, CE |
Communication Protocols | - |
Control Form | On / Off, P, PI, PD, PID |
Reading Frequency | 3 readings per second |
Accuracy | ± 0.25% of full scale for thermocouple, thermoresistance, mV, V and mA input. |
Optional Sensor Inputs | Selectable by configuration parameters 0-50 mV, 0-5 V, 0-10 V |
Selectable by configuration parameters 0-20 mA, 4-20 mA | |
Scale | - |
Sensor Inputs | Selectable by configuration parameters L (DIN43710), |
J, K, R, T, S, B, E, N (IEC584.1) (ITS90) | |
Supply Voltage and Power | 100-240 Vac (-15%,+10%) 50/60 Hz. 6 VA |
24 Vac (-15%,+10%) 50/60 Hz. 6 VA | |
24 Vdc (-15%,+10%) 6 W | |
Analogue Output | - |
Optional Outputs | - |
Relay Output | 5A@250 Vac at resistive load |
SSR Output | 17mA@25V Dc(Maximum) |
Dimensions | 96 mm x 96 mm x 87,5 mm |
Installation | Fixed Installation |
Protection Class | NEMA 4X (IP65 at front, IP20 at rear) |
Storage / Operating Humidity | 90 % max. (None condensing) |
Storage Temperature | 0...50ºC |
Have Any Questions ?